YEM3Z-125~800 Adjustable Type MCCB
Divided into two types:LCD Type and Knob Type
1.Operating environment
a.Do not install in an environment containing explosive gas,or there is a risk of explosion.
b.Do not install it in a place where rain or snow strikes.
C.Do not install it in a place where the vibration acceleration is greater than 0.7g.
d.Do not install in places where gas medium can corrode metal and destroy insulaton.
2.Circuit breaker installation place environmental requirements
Ambient air temperature:-5℃~+40°℃,and 24h average value does not exceed+35℃.
Relative humidity:The average minimum humidity of the wettest month Relative shall not exceed+25℃,and the average maximum relative temperature of the month shall not exceed humidity 90%,taking into account the condensation occuring on the surface of the product due to temperature changes
Altitude:Not exceeding 2000m
class of pollution:Level 3
3.Technical parameter
| type | YEM3Z-125 | YEM3Z-250 | YEM3Z-400 YEM3Z-630 | YEM3Z-800 | |||||||
| current frame | 125 | 250 | 400 | 630 | 800 | ||||||
| rated current In(A) | 32(12.5~32)/63(25~63) 125(50~125) |
250(100~250) | 400(160~400) | 630(250~630) | 800(315~800) | ||||||
| rated working voltage Ue(V) | AC415 | ||||||||||
| rated insulation voltage Ui(V) | 1000 | ||||||||||
| pole | 3 | 4 | 3 | 4 | 3 | 4 | 3 | 4 | 3 | 4 | |
| rated ultimate short-circuit reaking capacity Icu(kA) |
AC690V | 8 | 10 | ||||||||
| AC415V | 50 | 75 | |||||||||
| rated sevce shor-circuit reaking capacity Ics(kA) |
AC690V | 8 | 10 | ||||||||
| AC415V | 36 | 50 | |||||||||
| mechanical life | Mechanical maintenance | 40000 | 20000 | 10000 | |||||||
| Mechanical without maintenance | 20000 | 10000 | 5000 | ||||||||
| Outline dimension Unit:mm |
L | 150 | 150 | 165 | 165 | 259 | 259 | 259 | 259 | 281 | 281 |
| w | 92 | 122 | 107 | 142 | 140 | 184 | 150 | 198 | 211 | 281 | |
| H | 110 | 110 | 118 | 118 | 155 | 155 | 155 | 155 | 161 | 161 | |
| c-over distance(mm) | ≤50 | ≤100 | |||||||||
4.Product appearance and names of parts